Sign In | Join Free | My enlightcorp.com |
|
Model Number : TDT
Certification : ISO9001
Place of Origin : China
MOQ : 1 set Tan Delta Tester
Price : USD1.0
Payment Terms : T/T, Western Union
Supply Ability : 1000 sets per month
Delivery Time : 10 days
Packaging Details : Tan Delta Tester packed in veneer case
Item Name : TDT Automatic Multi-functional Power Transformer 10kV Tan Delta Tester
Functions : Test the tan delta and power factor of transformer
Applicable transformer : Single Phase and Three Phase Transformers
Features : Automatic, multi-functional tan delta tester
CVT range : 10-10000
Data storage : 200 groups
Size : 350(L)×270(W)×270(H)
Weight : 28kg
Power supply : AC220V ± 10%, 50Hz/60Hz
Warranty : One year
Service : OEM service is available
Equipped with a high-end full touch LCD screen, super touch interface, each process is very clear, the operator does not need additional professional training can be used. It is a ideal intelligent equipment for measuring dielectric loss.
The instrument is equipped with a calendar chip and large capacity memory, the test results can be stored, you can review the results at any time, and can print it out.
The instrument has high pressure, high voltage, standard, positive connection method and reverse connection method, self excitation method and other methods as optional; high voltage in standard high voltage conditions (greater than 10kV) dielectric loss.
The instrument can also test the full sealed CVT (capacitor voltage transformer) C1, C2 dielectric loss and capacitance, to achieve the C1, C2 simultaneous test. The instrument can also test the CVT ratio and voltage angle difference.
The instrument can accurately measure the dielectric loss and capacitance of CVT without dismantling the CVT high voltage lead.
The instrument can be used to measure the dielectric loss and capacitance value of C0 on the upper end of CVT.
The inverter and sampling circuit of the instrument are all controlled by digital, and the output voltage is adjustable continuously.
The instrument has many protection measures, such as input voltage fluctuation, output short circuit, over voltage, over current and temperature. The instrument also has the grounding detection function to ensure that no grounding equipment is not allowed to boost.
1 | Use conditions | -15℃∽40℃ | RH<80% |
2 | Anti-interference | Frequency conversion | |
3 | Power | AC 220V±10% | Allowable generator |
4 | High output | 0.5KV∽10KV | Every 0.1kV |
Precision | 2% | ||
Maximum current | 200mA | ||
Capacity | 2000VA | ||
5 | Self-excited power | AC 0V∽50V/15A | 45HZ/55HZ 47.5HZ/52.5Hz 55HZ/65HZ 57.5HZ/62.5H Automatic double frequency |
6 | Resolving power | tgδ: 0.001% | Cx: 0.001pF |
7 | Precision | △tgδ:±(Reading*1.0%+0.040%) | |
△C x :±(Reading*1.0%+1.00PF) | |||
8 | measuring range | tgδ | Unlimited |
C x | 15pF < Cx < 300nF | ||
10KV | Cx < 60 nF | ||
5KV | Cx < 150 nF | ||
1KV | Cx < 300 nF | ||
CVT test | Cx < 300 nF | ||
9 | CVT range | 10∽10000 | |
accuracy | 0.1% | ||
Resolving power | 0.01 | ||
10 | Exterior dimension | 350(L)×270(W)×270(H) | |
11 | Memory size | The 200 group supports U disk data storage | |
12 | Weight | 28 Kg |
![]() |
TDT Automatic Multi-functional Power Transformer 10kV Tan Delta Tester Images |